CTR K

Motor Sizing & VFD Calculator — Frame (IEC 60072-1), Torque & Energy Savings (IEC 60034-1)

Governing standard: IEC 60034-1· IEC 60034-1:2017 (rating & performance) · IEC 60072-1 (frame numbers & output series) · NEMA MG-1 · Kloss speed-torque formula · fan/pump affinity laws

Page last updated

How IEC 60034-1 works — the method explained

The MechanixCalc motor sizing calculator selects and verifies three-phase AC induction motors against IEC 60034-1 rating and performance terminology and the IEC 60072-1 standard output series, with NEMA MG-1 equivalents noted where they apply. Enter the load torque, speed, inertia and application type, and the tool returns the IEC 60072-1 frame size (0.25 kW to 250 kW), rated torque, full-load line current, starting current, a starting-torque check against the peak run-up demand and a stall check against the pull-out torque — all in one pass. The speed-torque characteristic is plotted from the Kloss (Boucherot) formula with selectable constant-torque, quadratic (fan/pump) and linear (compressor) load curve overlays.

A built-in VFD energy module quantifies annual electrical energy and cost savings using the fan/pump affinity laws across up to five speed bands, and a thermal derating panel applies altitude and ambient-temperature correction factors — common manufacturer practice built on the IEC 60034-1 reference site conditions — and checks the design power against that site-derated frame power (CHECK above 90 %, FAIL above 100 %), so a frame that is adequate at sea level but short at altitude or in a hot plant is flagged in the verdict and the report. The tool is aimed at machine designers, plant engineers and energy auditors who need a defensible, standards-cited motor specification — and a worked PDF report to hand to a reviewer.

What this calculator does

  • IEC 60072-1 frame selection: smallest standard IEC frame, from 0.25 kW to 250 kW, that covers the design power with the specified service factor — a design power above the top of the series is refused with an explanation, never silently capped at the largest frame
  • Starting-torque check on every application type: locked-rotor torque against the peak run-up demand (load torque plus acceleration torque), with an extra 1.6× breakaway margin required for hoists
  • Frame comparison table with separate breakaway (locked-rotor torque vs steady load) and run-up (peak demand vs that frame's pull-out torque) verdicts on every candidate size
  • Speed-torque characteristic (Kloss formula) with constant-torque, quadratic fan/pump and linear compressor load curve overlays, and automatic operating-point detection
  • VFD energy savings and CO₂ reduction by speed band — cube law for centrifugal fans and pumps, linear law for conveyors — with simple payback period
  • Thermal derating for altitude above 1000 m and ambient temperature above 40 °C, common manufacturer practice built on the IEC 60034-1 reference site conditions, plus a winding-temperature estimate taken at the design's own load (or at the nameplate service-factor load when no design load is set)
  • IE efficiency class comparison (IE1 through IE4) with annual energy-cost table
  • Starting analysis: DOL, star-delta, soft-starter and VFD starting current and torque comparison
  • IEC duty-type rating factor for S1 continuous, S2 short-time, S3 intermittent and S6 continuous-periodic duty — intermittent and short-time duty permit an up-rating — S2 by the thermal-time-constant equivalence (capped at 2.0); S3/S6 by a rough, conservative thermal rule that credits the reduced cooling of a stopped self-ventilated motor (S3) and the no-load losses of an idling one (S6), never above 1/√CDF and capped at 1.6 — confirm the S3/S6 rating with the motor manufacturer
  • Every panel validates its inputs: an unrecognised enclosure, insulation class, duty type or supply voltage, or an efficiency, power factor, torque, speed or service factor outside its physical range, is refused rather than returned as a plausible-looking number
  • Branded PDF engineering report with the governing method and all substituted values shown

Method & formulas

Motor sizing and IEC 60072-1 frame selection

The design power is the service factor times the load torque times the larger of the load speed and the motor's rated speed. A motor's rating is a torque at its rated speed, so a load that runs slower than that (a VFD in its constant-torque region, or a direct drive entered at a lower speed) is sized on its torque, not on its smaller shaft power; above rated speed it is sized on power. The tool then selects the smallest standard IEC frame — from the IEC 60072-1 frame numbers and standard output series, covering 0.25 kW to 250 kW — whose nameplate rating covers that design power. If the design power exceeds the top of that series, no frame is returned at all: the calculation is refused with an explanation rather than reporting the largest frame in the table as though it were adequate. The rated torque of the selected motor is back-calculated from the frame rating and the synchronous speed reduced by the assumed 3% full-load slip. The full-load line current is found from the motor nameplate power, the supply voltage, the power factor and the motor efficiency.

Three torque checks then feed the verdict. The load torque times the service factor must not exceed the continuous torque the frame delivers at the load speed. The locked-rotor torque of the selected motor (approximately 1.5 times rated for a standard squirrel-cage machine) must exceed the load torque, or the motor cannot start the load; hoists must additionally clear a 1.6× breakaway margin on the peak run-up demand — rated load torque plus the acceleration torque derived from the total moment of inertia and the required acceleration time. A stall check compares that peak demand against the pull-out (breakdown) torque (approximately 2.5 times rated); above the rated speed a VFD runs in field weakening, so the continuous torque is reduced in proportion to rated speed over load speed and the pull-out torque with its square. If the peak exceeds the available pull-out, the motor stalls during run-up. The frame comparison table reports breakaway and run-up separately for every candidate size, because a motor can break the load away and still stall while accelerating it.

Load shaft power
P_load = T_load × 2π × N_load / 60 × 10⁻³

where P_load = shaft power demanded by the load (kW); T_load = load torque (N·m); N_load = load speed (rpm)

Full-load line current (three-phase)
I_FL = P_selected × 10³ / (√3 × V × cosφ × η_m)

where I_FL = full-load current (A); P_selected = selected IEC frame rating (kW); V = line voltage (V); cosφ = power factor; η_m = motor efficiency (decimal)

Speed-torque characteristic (Kloss / Boucherot formula)

The motor torque as a function of slip is described by the Kloss formula, which passes through the rated point and the breakdown (pull-out) torque at the critical slip. MechanixCalc blends the Kloss curve toward the user-specified locked-rotor torque at standstill, giving a realistic full-range characteristic from zero to synchronous speed. The load curve overlay (constant, quadratic or linear) is plotted on the same axes, and the steady-state operating point is found by interpolating the crossing on the stable running branch above half-synchronous speed.

Kloss formula
T(s) = 2 × T_bd / (s / s_bd + s_bd / s)

where T(s) = motor torque at slip s; T_bd = breakdown (pull-out) torque; s_bd = slip at breakdown torque; s = per-unit slip = (N_sync − N) / N_sync

VFD energy savings (affinity laws) and site derating

For centrifugal fans and pumps, the shaft power scales with the cube of the speed ratio (the fan/pump affinity laws). Running a motor at reduced speed through a variable-frequency drive therefore cuts the shaft power — and the electrical input power — as the cube of the fractional speed. Conveyors are treated as a constant-torque load, where power falls linearly with speed and the saving is correspondingly smaller. MechanixCalc computes both the direct-on-line (DOL) electrical input power and the VFD electrical input power at each operating speed band, summing across all bands to give annual energy saved, annual cost saved, CO₂ avoided and the simple VFD payback period.

Thermal derating uses common manufacturer practice built on the IEC 60034-1 reference site conditions (1000 m altitude, 40 °C ambient): altitude above 1000 m reduces available power by 1% per 100 m of additional altitude; ambient temperature above 40 °C reduces available power by 1% per °C above 40 °C. These factors are applied multiplicatively to the rated nameplate power, and the nameplate service factor is then applied to give the available power.

The winding temperature beside that result is evaluated at the design's own load: the sized design power (application service factor kept) divided by the selected frame rating gives the load ratio L. At or above rated load the rated-load temperature rise is multiplied by L² (all losses scaled with load squared — the conservative member of the family above rated); below rated load it is multiplied by 0.5 + 0.5·L², which keeps a conservative 50 % share of the losses constant, since iron and windage losses do not fall with load. At L = 1 it is exactly the rated-load rise. Without a design load (or when the load runs below the motor's base speed on a VFD, where a self-ventilated motor cools less), the winding is evaluated at the nameplate service-factor load instead: the rated-load rise times the square of the service factor, never below the rated-load rise itself. The altitude and ambient factors are not folded into that ratio: they exist to hold the winding at the same rise despite degraded cooling, so including them would double-count and would report a cooler winding at altitude.

VFD shaft power at fractional speed (fan/pump affinity law)
P_VFD(n) = P_rated × (n / n_rated)³

where P_VFD = shaft power at reduced speed (kW); P_rated = rated shaft power (kW); n / n_rated = fractional speed ratio (0–1)

Ambient-temperature power derating (manufacturer practice)
k_temp = 1 − 0.010 × (T_amb − 40) for T_amb > 40 °C

where k_temp = power derating factor (0.80 at 60 °C); T_amb = ambient temperature (°C). Below 40 °C, k_temp = 1.0. Built on the IEC 60034-1 40 °C reference ambient; the 1%/°C reduction itself is common manufacturer practice, not a value prescribed by the standard.

Winding temperature at the design load
ΔT = ΔT_rated × f(L), f = L² (L ≥ 1), 0.5 + 0.5·L² (L < 1), L = P_design / P_rated · T_winding = T_amb + ΔT

where ΔT = winding temperature rise at the design load (°C); ΔT_rated = rise at rated load from the lumped loss/enclosure correlation (°C); L = design power over the selected frame rating (without a design load, L is replaced by max(1, SF), SF = nameplate service factor); T_amb = ambient temperature (°C); T_winding is a mean-winding estimate, so it is compared against the insulation-class temperature (B 130 °C, F 155 °C, H 180 °C — hot-spot limits) less a rough 15 K hot-spot allowance. The rated-load rise is a floor, so a nameplate service factor of 1.0 or below never reports a cooler winding than the machine's own rated-load rise.

Worked example

Select the IEC motor frame for a conveyor drive requiring 100 N·m at 1450 rpm with a service factor of 1.15.

Given

  • Load torque T_load100 N·m
  • Load speed N_load1450 rpm
  • Load inertia J_load2.5 kg·m²
  • Acceleration time t_acc5 s
  • Service factor SF1.15

Result

  • Selected IEC motor18.5 kW (4-pole, 50 Hz)
  • Rated torque T_rated121.4 N·m
  • Peak run-up torque T_peak183.5 N·m (T_start 182.1 N·m — no margin; T_pullout 303.5 N·m — clear)
  • Load utilisation94.7% of frame rating
  1. Calculate the load shaft power: P_load = T_load × 2π × N_load / 60 / 1000 = 100 × 2π × 1450 / 60 / 1000 = 100 × 151.84 / 1000 = 15.18 kW.
  2. Apply the service factor to the load torque at the larger of the load speed and the motor's rated speed (4-pole, 50 Hz → N_sync = 1500 rpm; the engine's fixed 3% rated slip gives N_rated = 1455 rpm, above the 1450 rpm load speed): P_design = 1.15 × 100 × 2π × 1455 / 60 / 1000 = 1.15 × 100 × 152.37 / 1000 = 17.52 kW.
  3. Select the smallest standard IEC frame ≥ 17.52 kW. The IEC series steps 15 → 18.5 kW, so the selected motor is 18.5 kW. (Had the design power exceeded 250 kW, the top of the series, the tool would refuse the calculation instead of returning 250 kW.)
  4. Calculate the rated torque of the selected motor at N_rated = 1455 rpm: T_rated = 18500 / (2π × 1455 / 60) = 18500 / 152.37 = 121.4 N·m, which covers the load torque times the service factor (1.15 × 100 = 115 N·m).
  5. Find the peak run-up demand: with the rotor inertia taken as 0.1 × J_load, J_total = 2.75 kg·m² and α = 2π × 1450 / (60 × 5) = 30.37 rad/s², so T_acc = 2.75 × 30.37 = 83.5 N·m and T_peak = 100 + 83.5 = 183.5 N·m.
  6. Check both torque margins against that peak. Pull-out torque T_pullout = 2.5 × 121.4 = 303.5 N·m comfortably exceeds the 183.5 N·m peak, so the motor will not stall during run-up, and the locked-rotor torque of 182.1 N·m (1.5 × 121.4, the conservative generic multiplier this tool applies) is well above the 100 N·m load, so the motor can start it — the torque checks the calculator runs all pass. Note however that 182.1 N·m sits essentially ON the 183.5 N·m peak demand, so this frame has no locked-rotor margin to spare against the accelerating load: enter the motor's real nameplate locked-rotor ratio before committing to it
  7. Load utilisation check: P_design / P_selected = 17.52 / 18.5 = 94.7% of frame. The tool flags anything above 90% of the frame rating, so this selection is banded CHECK, not clear: it leaves under 6% of headroom for a service factor already applied, and the next IEC step (22 kW) would sit at 79.6%.

Illustrative example using standard IEC series sizes and assumed 3% rated slip. Verify rated torque, starting torque, full-load current and thermal class against the motor manufacturer’s datasheet before specifying.

Frequently asked questions

Which standard does this motor sizing calculator use?

Frame and standard-output-series selection follow IEC 60072-1 (Dimensions and output series for rotating electrical machines — Part 1: Frame numbers 56 to 400 and flange numbers 55 to 1080). Rating, performance and duty-type definitions follow IEC 60034-1:2017 (Rotating electrical machines — Part 1: Rating and performance). Starting torque, pull-out torque and starting current use generic typical multipliers (1.5×, 2.5× and 6.5× respectively — the most conservative of the values the tool previously used in different places) in the terminology of IEC 60034-12, not that standard's tabulated design-N minima, which vary with rated power and pole count — verify against a manufacturer datasheet for final design. The output series carried here runs from 0.25 kW to 250 kW; a design power above 250 kW is refused outright rather than answered with the largest frame in the table, and duty types S1, S2, S3 and S6 are supported (S4, S5 and S7–S9 are refused rather than silently treated as continuous). Thermal derating for altitude and ambient temperature builds on the IEC 60034-1 reference site conditions (1000 m, 40 °C) using common manufacturer practice (1%/°C above 40 °C; 1%/100 m above 1000 m). The speed-torque curve is computed with the Kloss (Boucherot) formula, and VFD energy savings use the fan/pump affinity laws. NEMA MG-1 design-letter equivalents are noted where applicable.

How does the VFD energy saving calculation work?

For centrifugal fans and pumps, shaft power scales with the cube of the speed ratio (affinity law: P ∝ n³). Running at 75% speed cuts shaft power to about 42% of full-speed; at 50% speed, to only 12.5%. The calculator computes the DOL electrical input power (rated power ÷ motor efficiency) and the VFD electrical input power (affinity-law shaft power ÷ combined motor and inverter efficiency) at each speed band you enter, then sums the annual difference to give energy saved, cost saved and CO₂ avoided. Conveyors are handled as a constant-torque load, where power falls linearly rather than cubically with speed. Six of the panels — motor sizing, thermal derating, starting analysis, efficiency map, duty-cycle rating and drive-train reflection — carry engineering-estimate badges because they rely on empirical multipliers and typical curves rather than nameplate-specific data.

What is the difference between the IEC efficiency classes IE1 to IE4?

IE1 through IE4 are the IEC 60034-30-1 energy-efficiency classes for AC induction motors, where IE1 is standard, IE2 is high, IE3 is premium and IE4 is super-premium efficiency. IEC 60034-30-1 sets a minimum efficiency value at rated (100%) load for each class; the 50%/75%/100% part-load comparison points some efficiency labelling uses come from the EU Ecodesign regulation, not from the IEC standard itself. Under EU Ecodesign Regulation (EU) 2019/1781 as amended by (EU) 2021/341, IE3 is the minimum for most three-phase motors, but since 1 July 2023 motors rated 75–200 kW must meet IE4. The calculator's efficiency-map panel lets you compare annual running costs across all four classes at your actual operating load fraction and hours per year.

Can I check motor suitability for high-altitude or hot environments?

Yes. The thermal derating panel applies an altitude derating (−1% per 100 m above the IEC 60034-1 reference altitude of 1000 m) and an ambient-temperature derating (−1% per °C above the IEC 60034-1 reference ambient of 40 °C) to the nameplate rating — common manufacturer practice built on those reference site conditions — and checks the sized design power against that site-derated power: above 90 % reads CHECK and above 100 % reads FAIL in the verdict and the report. You can also enter the insulation class (B, F or H), enclosure type (TEFC, ODP or TENV), nameplate service factor and rated efficiency to estimate the mean winding temperature and check it against the insulation temperature limit (130 °C, 155 °C or 180 °C, hot-spot values) less a rough, conservative 15 K hot-spot allowance. That winding temperature is evaluated at the design's own load (the sized design power over the frame rating): the rated-load rise is scaled by the load ratio squared above rated load and by 0.5 + 0.5 × the load ratio squared below it, a conservative allowance for losses that do not fall with load. With no design load set it is evaluated at the nameplate service-factor load instead. The enclosure factor is a lumped allowance rather than a pure cooling coefficient: because the model scales the cooling surface from the machine's rating rather than its physical frame, the factor also absorbs the frame-oversize a lower-rated enclosure carries in the same frame. TEFC is the reference; ODP carries a modest allowance for the in-service fouling of an open air path, and TENV sits between them.

Is the motor sizing calculator free?

You can use it during a free 30-minute preview with no sign-up, and a free 14-day account trial unlocks every calculator with no credit card required. The branded PDF engineering report and saved calculations are included in the free 14-day trial and in every paid plan.

Run the Motor Sizing & VFD on your own numbers

Free 30-minute preview — no sign-up. A free 14-day account trial unlocks every tool and the branded PDF report, no credit card required.

Start free

Using MechanixCalc at work? See plans & pricing — one subscription unlocks all 50+ calculators, PDF reports and saved projects.